—utility details equipment deterioration and repeated failed attempts to restore supply
A defective recently installed cable was identified before electricity restoration began in East Berbice on Saturday, Guyana Power and Light Inc. (GPL) said, outlining a prolonged troubleshooting exercise that also uncovered deteriorated equipment, moisture and a damaged auxiliary transformer at its Canefield Substation.
In a detailed account yesterday of the outage, GPL said technicians ultimately disconnected the defective cable and returned an older, serviceable cable to operation, allowing customer circuits to be progressively restored after almost two days without electricity.
The company’s explanation follows public demands for accountability and President Irfaan Ali’s announcement of a 50 per cent reduction in affected customers’ November bills and an investigation into the failure and GPL’s response.
According to GPL, the outage began at approximately 8.14 pm on Thursday, November 19, when an incoming supply connection tripped, cutting all circuits and locking out the substation’s 13.8-kilovolt distribution bus.
A flash was subsequently reported from another equipment cubicle during attempts to restore the system. A specialised technical team was dispatched and began investigating during the early hours of Friday.
GPL said technicians conducted controlled switching, tested voltage-measuring transformers, inspected the busbar system and repaired areas showing deterioration or electrical tracking.
The investigation uncovered deteriorated transformers, condensation within the SG2 switchgear cubicle, suspect insulation and components, and poor insulation-resistance readings from some equipment.
Components were cleaned, repaired, re-insulated and tested, with replacements made where necessary. However, repeated attempts to restore power continued to trigger protective shutdowns.
The ST2 auxiliary transformer was identified as damaged and disconnected. Removing it did not resolve the recurring fault, GPL said.
“However, another attempt to energise the bus with ST2 removed resulted in the same trip, indicating that ST2 was not the only cause of the recurring system fault,” the company stated.
Reassembled
Troubleshooting continued overnight into Saturday, with equipment dismantled, tested and reassembled. Specialist assistance was also engaged to test the busbar, grounding transformer, switches and associated equipment.
GPL said the work included extensive refurbishment of the SG2 panel at the substation, which was constructed in 1975, using available spare components.
The critical indication emerged at approximately 3.30 pm on Saturday, when technicians observed electrical arcing beneath metal covers over a recently installed 500-square-millimetre cable during another attempt to energise the system. A protection relay also registered a trip.
“This development redirected the technical investigation towards the cable,” GPL said.
Insulation-resistance testing subsequently confirmed that the cable’s B-phase was defective, with a short circuit to ground.
Technicians then tested the previously installed 400-square-millimetre incoming cable and found it suitable for reuse. Work began at approximately 6 pm to reconnect it between the 60-megavolt-ampere transformer and the switchgear.
At 6.25 pm, the team successfully closed the bus tie, permitting phased restoration of customer feeders to begin. That was approximately 46 hours after the initial shutdown.
GPL said feeders F1 and F4 were energised to restore supply from New Amsterdam to Mara, followed by F3, serving customers between Canje and Williamsburg.
Work continued after the main system was restored because the substation’s auxiliary supply remained unavailable following the removal of the damaged ST2 transformer. A replacement arrangement was completed at approximately 1.30 am on Sunday.
The release does not identify when the defective cable was installed, what caused its failure or the results of any testing before it entered service. It also does not specify when the other equipment deficiencies first developed.
GPL apologised to affected households and businesses, acknowledged its technical personnel’s sustained efforts and said it would review the outage and the deficiencies identified, with the aim of improving reliability and preventing similar prolonged disruptions.
President Irfan Ali on Sunday announced the bill reduction for approximately 15,000 affected customers. He said an investigation must establish what went wrong, assess the response and identify measures to prevent a recurrence, with its findings determining any consequential action.
Ali also called for stronger emergency arrangements and clearer communication, particularly to protect hospitals, water supply and other essential services.
The blackout left residents and businesses counting losses from spoiled food, disrupted trading and the absence of refrigeration.
New Amsterdam Market vendor Renay Haywood told Kiskadee Watch that groceries had to be discarded and chickens her parents had prepared for sale were lost. Bar owner Onawa Harvey described trying to operate with solar lighting, which made it difficult for customers to recognise that her business was open.
The Berbice Chamber of Commerce and Development Association also demanded a detailed explanation of the failure, the reasons restoration took so long and a comprehensive plan to prevent a recurrence.